Flue Gas Analyzer w/ NOX - TPI®
The TPI Flue Gas Analyzer will work with high efficiency furnaces, hot water heaters, and other combustible gas appliances!
Features & Applications
The TPI Flue Gas Analyzer with NOX is an all in one instrument designed to maximize diagnostic efficiency and accuracy.
Features:
- Measure O2, CO, and NO
- Calculate CO2, NOX, efficiency, excess and air ratio
- Will work with high efficiency furnaces, hot water heaters, and other
combustible gas appliances - Dual input K-type thermocouple temperature tester
- Dual input differential manometer with 3 selectable units of measure:
kPa, mBar, inH2O - Protective rubber boot
- Soft carrying case
Spec Summary:
| Temperature Measurement | |
| Range | -50° to 1000°F, or ?C |
| Resolution | 1°F or C |
| Accuracy (K-type) | -0.3%, ±2°F or ±1*C |
| Nitric Oxide (NO) Measurement | |
| Range | 0 to 5,000 ppm |
| Resolution | 1 ppm |
| Accuracy | <100 ppm: ±5 ppm <1000 ppm: ±5% >1000 ppm: ±10 ppm |
| NOX Measurement | |
| Range | 0 to 5,250 ppm |
| Resolution | 1 ppm |
| Accuracy | Calculated |
| Gross/Net Efficiency | |
| Range | 0 to 100% |
| Resolution | 0.1% |
| Accuracy | Calculated |
| Oxygen (O2) Measurement | |
| Range | 0 to 25% |
| Resolution | 0.1% |
| Accuracy | ±0.3% |
| Carbon Monoxide (CO) Measurement | |
| Range | 0 to 10,000 ppm |
| Resolution | 1 ppm |
| Accuracy | < 100 ppm CO: ±5 ppm >100 ppm CO: ±5% of reading |
| Carbon Dioxide (CO2) Measurement | |
| Range | 0 to 25% |
| Resolution | 0.1% |
| Accuracy | Calculated |
| CO/CO2 Ratio | |
| Range | 0 to 0.999 |
| Resolution | 0.001 |
| Accuracy | Calculated |
| Instrument Specifications | |
| Operating Temperature Range | 14 to 122°F (-10 to 50°C) |
| Battery | 4 AA Batteries |
| Fuels | Natural Gas, LPG, Light Oil, Heavy Oil |
| Display | Backlit LCD |
| Data Storage | 10 sets of readings |
| Time & Date | 24 Hour Real Time Clock |
| Dimensions | 7.87" x 3.54" x 2.36" (200mm x 90mm x 60mm) |
| Weight | 1.1 lb. (500g) |
| Switch Off | Failsafe |
| Exhaust | Safety Spigot |
| Conforms To | BS7927 (and the draft BS7967) |